| Plan Review Notes For Permit 02091026 |
| Permit Number |
02091026 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-30 00:00:00 | PLEASE PROVIDE A CONSTRUCTION DETAIL FOR | | | THE CUTTING OF THE FLOOR/CEILING | | | ASSEMBLIES FOR THE PROPOSED HOOD VENT | | | SYSTEM.INCLUDE SHAFT CONSTRUCTION | | | DETAILS AND FIRE DESIGN NUMBERS.SEE | | | FBC 705.2. | | | | | | PROVIDE A SPECIFIC CONSTRUCTION DETAIL | | | FOR THE SOFFIT SHOWN ON SHEET A3. | | | INCLUDE CONNECTIONS TO THE EXISTING | | | STRUCTURE ABOVE.SEE FBC 104.2.1. |
|