2002-09-30 00:00:00PLEASE PROVIDE A CONSTRUCTION DETAIL FOR
 THE CUTTING OF THE FLOOR/CEILING
 ASSEMBLIES FOR THE PROPOSED HOOD VENT
 SYSTEM.INCLUDE SHAFT CONSTRUCTION
 DETAILS AND FIRE DESIGN NUMBERS.SEE
 FBC 705.2.
  
 PROVIDE A SPECIFIC CONSTRUCTION DETAIL
 FOR THE SOFFIT SHOWN ON SHEET A3.
 INCLUDE CONNECTIONS TO THE EXISTING
 STRUCTURE ABOVE.SEE FBC 104.2.1.