| Plan Review Notes For Permit 02090928 |
| Permit Number |
02090928 |
|
| Review Stop |
FIRE |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2003-11-24 00:00:00 | 1) THE FIRE HYDRANT INSTALLED IN THE | | | REAR DISPLAYS FOUR CONCRETE BOLLARDS. | | | THE BOLLARDS SHALL ALLOW FOR 7'-6" | | | CLEARANCE TO THE FRONT AND SIDE OF IT. | | | FOUR FEET CLEARANCE IS REQUIRED TO THE | | | REAR OF THE HYDRANT. | | | | | | 2) ALL WELDING PERFORMED ON SITE MUST | | | BE APPROVED BY THE BUREAU OF FIRE | | | PREVENTION. ALL WELDING SHALL COMPLY | | | WITH NFPA 51B, THE STANDARD FOR CUTTING | | | AND WELDING. NO COMBUSTIBLE MATERIAL | | | IS ALLOWED WITHIN 35 FEET OF ANY | | | WELDING ACTIVITIES. | | | | | | 3) BUILDING ADDRESS NOTE SHOWN ON | | | ELEVATION DRAWINGS SHOULD INDICATE | | | 6" HIGH NUMERALS. | | | | | | 4) PLEASE PROVIDE PRODUCT APPROVALS | | | FOR ROLLING FIRE DOOR. | | | | | | 5) THE EXTERIOR GATES DO NOT HAVE TO | | | OPEN WHEN THE FIRE ALARM SYSTEM | | | ACTIVATES. | | | | | | 6) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM SYSTEM. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|