Plan Review Notes
Plan Review Notes For Permit 02090928
Permit Number 02090928
Review Stop FIRE
Sequence Number 5
Notes
Date Text
2003-11-24 00:00:001) THE FIRE HYDRANT INSTALLED IN THE
 REAR DISPLAYS FOUR CONCRETE BOLLARDS.
 THE BOLLARDS SHALL ALLOW FOR 7'-6"
 CLEARANCE TO THE FRONT AND SIDE OF IT.
 FOUR FEET CLEARANCE IS REQUIRED TO THE
 REAR OF THE HYDRANT.
  
 2) ALL WELDING PERFORMED ON SITE MUST
 BE APPROVED BY THE BUREAU OF FIRE
 PREVENTION. ALL WELDING SHALL COMPLY
 WITH NFPA 51B, THE STANDARD FOR CUTTING
 AND WELDING. NO COMBUSTIBLE MATERIAL
 IS ALLOWED WITHIN 35 FEET OF ANY
 WELDING ACTIVITIES.
  
 3) BUILDING ADDRESS NOTE SHOWN ON
 ELEVATION DRAWINGS SHOULD INDICATE
 6" HIGH NUMERALS.
  
 4) PLEASE PROVIDE PRODUCT APPROVALS
 FOR ROLLING FIRE DOOR.
  
 5) THE EXTERIOR GATES DO NOT HAVE TO
 OPEN WHEN THE FIRE ALARM SYSTEM
 ACTIVATES.
  
 6) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL