Plan Review Notes
Plan Review Notes For Permit 02090928
Permit Number 02090928
Review Stop P
Sequence Number 3
Notes
Date Text
2003-04-15 00:00:00PASSED/PROVISO
  
 SEPARATE GAS PERMIT REQUIRED - THE
 FOLLOWING INFORMATION REQUIRED AT TIME
 OF GAS APPLICATION.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).