Plan Review Notes
Plan Review Notes For Permit 02090928
Permit Number 02090928
Review Stop M
Sequence Number 3
Notes
Date Text
2003-11-24 00:00:00DENIED:
 1.PER 2001 FBC(M) 307.2.3, THE
 AUXILIARY DRAIN LINE SHALL TERMINATE AT
 A CONSPICUOUS POINT TO SERVE AS AN ALARM
 THAT THE PRIMARY DRAIN IS RESTRICTED.
 PLAN P5 INDICATES AUXILIARY DRAIN
 TERMINATING AT THE SAME POINT AS THE
 PRIMARY DRAIN.THIS DOES NOT COMPLY
 WITH CODE REQUIREMENTS.PLEASE
 CORRECT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.