2003-03-22 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) SHT U1 DRYWELL SHALL BE MINIMUM OF
 12" FROM BLDG SECTION 1503.4.4. SURFACE
 WATER SHALL NOT DRAIN INTO DRYWELL. A
 RELIEF VENT WILL BE REQUIRED AS LINE
 ENTERS DRYWILL OR EXITS BLDG AT GROUND.
 2) SHT P-5, WHERE THE CONDENSATE DRAIN
 PIPES FROM MORE THAN ONE UNIT ARE MANI-
 FOLDED TOGETHER , THE PIPE OR TUBING
 SHALL BE SIZED IN ACCORDANCE WITH AN
 APPROVED METHOD. CONDENSATE WASTE AND
 DRAIN LINES SHALL NOT DECREASE IN SIZE
 FROM THE DRAIN PAN CONNECTION.
 3) PLEASE CLAIRFY USE FOR DEMUCKING
 PUMP. IS THERE PIPING CONNECTED TO THE
 PUMP?
 4) BACKFLOW PREVENTORS ARE REQUIRED FOR
 EACH BLDG. ONLY ONE IS SHOWN.
 5) THREE COMMENTS CONCERNING GAS REVIEW
 WERE NOT ADDRESSED. DO YOU WISH TO NOT
 REVIEW GAS AT THIS TIME AND ADDRESS
 THESE COMMENTS WHEN GAS PERMIT IS
 APPLIED FOR?
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377