Plan Review Notes
Plan Review Notes For Permit 02090928
Permit Number 02090928
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2003-02-26 00:00:001) EXISTING FIRE HYDRANT ON PAGE A0.2
 APPEARS TO BE POSITIONED DIRECTLY NEXT
 TO THE LUBRICATION TANK CONTAINMENT
 AREA. FIRE HYDRANTS ARE NOT TO BE
 POSITIONED NEXT TO POTENTIAL HAZARDS
 AND MINIMUM CLEARANCES ARE REQUIRED TO
 THEM PER STATE LAW.
  
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR NEW ABOVEGROUND 1000 GALLON FUEL
 TANK. WHEN SUBMITTED PRODUCT APPROVALS
 AND CUT SHEETS ARE TO BE PROVIDED.
  
 3) GATES THAT FIRE AND PARAMEDICAL
 EQUIPMENT ARE EXPECTED PASS THRU MUST
 BE AT LEAST 20 FEET IN CLEAR WIDTH.
  
 4) PLEASE BE ADVISED THAT ALL CUTTING
 AND WELDING IS TO BE PERFORMED IN
 ACCORDANCE WITH NFPA 51B, THE STANDARD
 FOR CUTTING AND WELDING. A MINIMUM OF
 35 FOOT CLEARANCE TO ANY AND ALL
 COMBUSTIBLE MATERIAL OR FLAMMABLE
 MATERIALS SHALL BE PROVIDED. NO
 CUTTING OR WELDING IS TO BE PERFORMED
 WITHOUT PRIOR FIRE DEPARTMENT APPROVAL.
  
 5) SEPARATE PLANS AND PERMITS FOR ANY
 SECURITY GATES OR FENCES.
  
 6) TYPICAL FIRE HYDRANT CONNECTION SHOWS
 A MINIMUM FROM A HYDRANT TO A BOLLARD
 AS THREE FEET. IT SHOULD BE AT LEAST
 FOUR FEET.
  
 7) ELECTRONIC SWITCHES ARE REQUIRED ON
 OS&Y CONTROL VALVES FOR FIRE LINES.
  
 8) FLOOR PLAN SHOULD IDENTIFY AREAS
 FOR POTENTIAL CUTTING AND WELDING
 OPERATIONS.
  
 9) BUILDING ELEVATION SHALL SHOW
 LOCATION OF ADDRESS.
  
 10) PLEASE INDICATE IF ANY FLAMMABLE
 OR COMBUSTIBLE LIQUIDS WILL BE STORED
 IN THE BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910