Plan Review Notes
Plan Review Notes For Permit 02090928
Permit Number 02090928
Review Stop E
Sequence Number 2
Notes
Date Text
2003-02-21 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE SEE 700-12E FOR CIRCUIT-
 ING OF EM/EXT LTS, PLEASE CLARIFY
 SHOWING GOING THRU C2 CONTACTOR??
 MAY NOT BE SWITCHED. PLANS NEED TO
 CLARIFY OR NOTE, TO BE ON LINE SIDE OF
 CIRCUIT IN CONTACTOR.
  
 2)NOTE: PLEASE SEE NOTE 2 OF FIRST
 REVIEW, PLEASE NOTE CLASS/DIVISION NOTE
 ON PLAN. IT IS NOTED RECEPTS TO BE AT
 24 ", BUT NEEDS TO NOTE ANY BELOW
 TO BE INSTALLED PER 511.
  
 3)NOTE: PLEASE CLARIFY LOAD SHOWN ON
 LOAD ANALYSIS FOR RECEPTS? 220-13
  
 4)NOTE: RESPONSE TO NOTE 7 FROM REVIEW
 SHOWS TRANSFORMER BEING BONDED TO COLD
 WATER. PLEASE NOTE IF ANY OF THE COLD
 WATER LINE IS BROKEN WITH THE USE OF
 PVC/CPVC OR INTERUPTED BY REPAIR, THE
 TRANSFORMER WOULD NOT HAVE A GROUND.
 PLEASE SHOW GOING TO EFFECTIVE GROUND/
 BLDG/FOOTER STEEL.THERE IS AN EXCEPT TO
 USE METAL CWP, HOWEVER, PLEASE SEE FIRST
 PART OF THIS NOTE, THIS HAS HAPPENED
 IN THE PAST AND HAS CREATED A LIFE
 SAFETY ISSUE.
  
 5)NOTE: PLEASE ALSO SHOW GROUNDING AT
 WASH BLDG. IT SHOWS AN EQUIPMENT GROUND
 FROM MAIN BLDG, PLEASE SHOW BONDING OF
 FOOTER STEEL AND COLD WATER.
  
 PLANS HAVE MOST COMMENTS ADDRESSED AND
 ARE IN GOOD SHAPE. PLEASE SUBMIT THE
 ABOVE INFORMATION FOR REVIEW. IF THERE
 ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372