| 2003-02-21 00:00:00 | ************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE 700-12E FOR CIRCUIT- |
| | ING OF EM/EXT LTS, PLEASE CLARIFY |
| | SHOWING GOING THRU C2 CONTACTOR?? |
| | MAY NOT BE SWITCHED. PLANS NEED TO |
| | CLARIFY OR NOTE, TO BE ON LINE SIDE OF |
| | CIRCUIT IN CONTACTOR. |
| | |
| | 2)NOTE: PLEASE SEE NOTE 2 OF FIRST |
| | REVIEW, PLEASE NOTE CLASS/DIVISION NOTE |
| | ON PLAN. IT IS NOTED RECEPTS TO BE AT |
| | 24 ", BUT NEEDS TO NOTE ANY BELOW |
| | TO BE INSTALLED PER 511. |
| | |
| | 3)NOTE: PLEASE CLARIFY LOAD SHOWN ON |
| | LOAD ANALYSIS FOR RECEPTS? 220-13 |
| | |
| | 4)NOTE: RESPONSE TO NOTE 7 FROM REVIEW |
| | SHOWS TRANSFORMER BEING BONDED TO COLD |
| | WATER. PLEASE NOTE IF ANY OF THE COLD |
| | WATER LINE IS BROKEN WITH THE USE OF |
| | PVC/CPVC OR INTERUPTED BY REPAIR, THE |
| | TRANSFORMER WOULD NOT HAVE A GROUND. |
| | PLEASE SHOW GOING TO EFFECTIVE GROUND/ |
| | BLDG/FOOTER STEEL.THERE IS AN EXCEPT TO |
| | USE METAL CWP, HOWEVER, PLEASE SEE FIRST |
| | PART OF THIS NOTE, THIS HAS HAPPENED |
| | IN THE PAST AND HAS CREATED A LIFE |
| | SAFETY ISSUE. |
| | |
| | 5)NOTE: PLEASE ALSO SHOW GROUNDING AT |
| | WASH BLDG. IT SHOWS AN EQUIPMENT GROUND |
| | FROM MAIN BLDG, PLEASE SHOW BONDING OF |
| | FOOTER STEEL AND COLD WATER. |
| | |
| | PLANS HAVE MOST COMMENTS ADDRESSED AND |
| | ARE IN GOOD SHAPE. PLEASE SUBMIT THE |
| | ABOVE INFORMATION FOR REVIEW. IF THERE |
| | ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |