| Plan Review Notes For Permit 02090928 |
| Permit Number |
02090928 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-07 00:00:00 | DENIED: | | | | | | 1.PROVIDE INFORMATION ON THE "SERVICE" | | | AREA - WILL THIS BE TO REPAIR | | | EQUIPMENT?PLEASE CLARIFY. | | | | | | 2.PLAN SHEET M3 OUTSIDE AIR PROVISIONS | | | AS PER 2001 FBC(M) TABLE 403.3 OR | | | ASHRAE 62-89 THE OUTSIDE AIR | | | CALCULATION SHALL BE 20 CFM PER | | | PERSON FOR OFFICE, CONFERENCE ROOMS, | | | ETC. NOT 15 CFM AS INDICATED. | | | PLEASE REVISE PLANS FOR ALL AREAS- | | | OFFICE, CONFERENCE, RESTROOMS, | | | LOCKER ROOM ETC. | | | | | | 3.PROVIDE MANUFACTURER INSTALLATION | | | INSTRUCTIONS FOR THE POWER WASHER & | | | FLUE. | | | | | | 4.CLARIFY CONDENSATE & AUXILIARY DRAIN | | | ARE BEING RUN TOGETHER & TERMINATING | | | AT MOP SINK ? (PLAN SHEET P-1). | | | AS PER 2001 FBC(M) 307.2.1, UNITS | | | GREATER THAN 6 TON SHALL DISCHARGE | | | STORM DRAIN OR DRYWELL. CONDENSATE | | | DRAINS MANIFOLDED TOGETHER, SHALL BE | | | SIZED TOGETHER BY AN APPROVED | | | METHOD.PLEASE PROVIDE CALCULATIONS | | | 2001 FBC(M) 307.2.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|