| 2002-09-19 00:00:00 | **************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE NOTE LABELING OF CIRCUITS |
| | ON PANEL SCHEDULE. PLEASE ALSO NOTE |
| | LABELING OF EM LTS/EXITS LTS PER 700-12. |
| | |
| | 2)NOTE: IT IS NOTED THAT PLAN SHOWS/NOTE |
| | -S ALL RECEPTS 24" AFF. PLEASE LIST |
| | CLASS/DIVISION. PER ART 500. |
| | |
| | 3)NOTE: PLEASE LIST/CLARIFY PANELS "H" |
| | AND "P1? ARE PANEL FEED-THRU? PLEASE |
| | SEE 384-15 |
| | |
| | 4)NOTE; PLEASE CLAIRY "SHOW" WINDOW |
| | OUTLETS REQ`D PER 210-62. PLEASE ALSO |
| | LIST ON PANEL SCHEDULE. |
| | |
| | 5)NOTE: PLEASE NOTE THAT PER FS/FAC |
| | 553-79 (6)(A) PLANS ARE REQ`D TO BE |
| | SIGNED,DATED, AND SEALED BY A PE. |
| | PLEASE ALSO NOTE PLANS HAVE A TITLE |
| | BLOCK FROM AN ENGINEER THEREFORE REQ`D |
| | TO BE SIGNED, DATE AND SEALED PER FAC/FS |
| | 61G15-23.002. |
| | |
| | 6)NOTE: PLEASE NOTE, PANELS ARE SHOWING |
| | ALL LOAD CALCS AT CONN LOADS. |
| | PLEASE NOTE THAT LOAD CALCULATIONS ARE |
| | REQ`D TO BE SHOWN PER 215-5. PLEASE |
| | NOTE, 220-3,220-10,220-11,220-13, PLEASE |
| | ALSO NOTE ALL CONTINUOUS LOADS ARE TO |
| | BE SHOWN AT 125%. 215-3,230-42. |
| | |
| | 7)NOTE; PLEASE PROVIDE INFORMATION AND/ |
| | OR SHOW GROUNDING ELECTRODE SYSTEM PER |
| | 250-50. BLDG/FOOTER STEEL, COLD WATER, |
| | GRND RODS? PLEASE ALSO NOTE GROUNDING |
| | ELECTRODE SYSTEM FOR DETACHED BLDG PER |
| | 250-32. |
| | PLEASE SHOW DEATIL FOR GROUNDING OF |
| | TRANSFORMERS PER 250-31. |
| | |
| | 8)NOTE:IT IS NOTED THAT AIC RATINGS ARE |
| | SHOWN ON PANELS. PLEASE PROVIDE AIC |
| | RATINGS FOR ALL NEW EQUIPMENTS. |
| | MAINS/PANELS/BRKRS MUST BE RATED FOR |
| | AVAILABLE FAULT CURRENT. 110-9. |
| | |
| | 9)NOTE: PLEASE CLARIFY LOADS BEING |
| | SHOWN ON PANEL SCHEDULES AND NOTHING |
| | BEING LISTED ON PANELS SCHEDULE? |
| | |
| | 10)NOTE:PLEASE SEE ANY COMMENTS FROM |
| | OTHER REVIEWERS THAT MAY HAVE AN AFFECT |
| | ON THE ELECTRICAL PLANS AND/OR LAYOUT.? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |