| Date |
Text |
| 2002-10-28 00:00:00 | PAID PLAN REVIEW, NOT A PERMIT |
| | APPLICATION. |
| | |
| | AT THE TIME OF PERMIT APPLICATION A |
| | RECENT PROPERTY SURVEY AND A SITE PLAN |
| | WITH DIMENSIONS LOCATING ALL OF THE |
| | STRUCTURES RELATIVE TO THE PROPERTY |
| | LINES AND EACH OTHER WILL BE NECESSARY. |
| | |
| | SHOW THE DESIGN INFORMATION FOR THE |
| | PRE-ENGINEERED BUILDINGS. |
| | |
| | ALL GLAZED PORTIONS OF THE EXTERIOR WALL |
| | AND ROOF OF THE BUILDING MUST COMPLY |
| | WITH THE HURRICANE MISSILE IMPACT |
| | RESISTANCE REQUIREMENTS OF FBC 1606.1.4 |
| | INCLUDING THE TRANSLUCENT PANELS.SEE |
| | ALSO FBC 2604.4 RE: WALL PANELS. |
| | |
| | THE ARCHITECTURAL SHEET A6.3 DECLARES |
| | EXPOSURE B, AND S1 CITES EXPOSURE C. |
| | PLEASE CLARIFY WHO WILL BE ENGINEER OF |
| | RECORD AND WHAT PORTIONS OF DESIGN ARE |
| | TO BE DELEGATED. |
| | |
| | SHOW THE STRUCTURAL INFORMATION FOR THE |
| | OVER HEAD CRANE. |
| | |
| | SHEET A 4.1 SHOWS VARIOUS EXTERIOR WALL |
| | ASSEMBLIES.PROVIDE THE STRUCTURAL |
| | DETAILS AS TO THE TYPE OF CONNECTIONS |
| | AND THE LOADS TRANSFERRED TO THE METAL |
| | BUILDING SYSTEM. |
| | |
| | WHAT IS THE MATERIAL CALLED OUT AS >>1" |
| | MASONRY MAT CONT AS SPECIFIED<< ON |
| | SHEET A4.1 AND ELSEWHERE? |
| | |
| | HOW WERE THE DOOR AND WINDOW PRESSURES |
| | ON SHEET A6.3 DETERMINED? |
| | |
| | SHEET A6.2, HOW ARE THE VARIOUS DOOR AND |
| | WINDOW HEADER/SILL,ETC. ATTACHED TO |
| | THE BUILDING? |
| | |
| | SHEET S1 CALLS FOR FOOTINGS TO BE POURED |
| | WITHOUT FORMS.CITY AMENDMENTS TO FBC |
| | 1804.1.1 REQUIRE ALL FOOTINGS AND |
| | CONCRETE PADS TO BE FORMED FULL DEPTH. |
| | PLEASE REVISE AS NECESSARY. |
| | |
| | SHOW THE DESIGN INFORMATION FOR THE |
| | REINFORCED MASONRY, IE F'M, GROUT |
| | STRENGTH, ETC.SEE FBC 2103.1. |
| | |
| | SHOW THE PROVISIONS FOR TERMITE |
| | PROTECTION IN ACCORDANCE WITH FBC |
| | 1816.1.7. |