2003-03-11 00:00:00NEW PLANS DATED 3/5/03 PREPARED BY A
 PATTERSON DRAFTSMAN.
  
 PROVIDE A ROOF FRAMING PLAN.SEE FBC
 104.2
  
 SHOW A DETAIL FOR THE STRUCTURALLY
 CONTINUOUS GABLE END WALL IN ACCORDANCE
 WITH FBC 2117.1.
  
 HOW WILL THE TRUSS ANCHORS BE CONNECTED
 TO THE EXISTING CONSTRUCTION?
  
 SHOW THE CALCULATION AND SIZING FOR THE
 ATTIC VENTILATION AS REQUIRED BY FBC
 2309.7.SEE 2309.6 FOR SIZE OF ATTIC
 ACCESS.
  
 SHOW THE DESIGN PRESSURES FOR THE ROOF
 COVERING.
  
 PLANS ARE TO BE REVIEWED BY A STRUCTURAL
 ENGINEER FOR STRUCTURAL ADEQUACY, AND
 SIGNED, SEALED AND DATED.