Plan Review Notes
Plan Review Notes For Permit 02090801
Permit Number 02090801
Review Stop B
Sequence Number 1
Notes
Date Text
2002-10-10 00:00:00PROVIDE A DETAIL FOR THE ATTACHMENT OF
 THE NEW TRUSSES TO THE EXISTING ROOF
 STRUCTURE.INCLUDE AN ANALYSIS OF THE
 EXISTING ROOF SYSTEM'S ABILITYTO
 ASSUME THE ADDED LOADING.SEE FBC 104.2
  
 SHOW THE ATTIC ACCESS AND VENTILATION
 INACCORDANCE WITH FBC 2309.6 AND FBC
 2309.7
  
 SHOW AN EXISTING OR PROVIDE A NEW
 EMERGENCY EGRESS AS REQUIRED BY FBC
 1005.4 FOR THE BEDROOM ON THE NORTH
 SIDE IN THE EXISTING HOUSE.
  
 PROVIDE A SOFFIT/OVERHANG CONSTRUCTION
 DETAIL.
  
 SEVERAL OF THE PRODUCT APPROVALS ARE
 EXPIRED OR ILLEGIBLE.PROVIDE CURRENT
 REPORTS WITH THE COMPONENTS MARKED
 WHERE NECESSARY, FOR THE EXTERIOR
 DOORS, WINDOWS AND ROOF COVERING.
  
 PROVIDE HURRICANE SHUTTERS OR IMPACT
 RESISTANT GLAZING FOR THE EXTERIOR WALL
 GLAZED OPENINGS.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO THE
 COUNTY, THE PERMIT PLANS STAMPED BY
 THAT OFFICE, AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 THE DECARED $7000.00 VALUATION FOR THIS
 SCOPE OF WORK IS TOO LOW, THE CITY
 ESTIMATE IS $20,226.00.PLEASE PAY AN
 ADDITIONAL $270.91 PERMIT FEE TO THE
 CITY.