| Notes |
| Date |
Text |
| 2002-10-01 00:00:00 | SINCE A SINGLE FIRE SPRINKLER SYSTEM | | | WILL BE PROTECTING BOTH BUILDINGS IT | | | IS CRITICAL THAT THE AREA OF PROTECTION | | | NOT BE EXCEEDED. PLEASE INDICATE WHAT | | | THE TOTAL AREA BEING PROTECTED FOR BOTH | | | BUILDINGS WILL BE AS IT RELATES TO A | | | SINGLE SUPPLY AND RISER SYSTEM. | | | | | | NO INDICATION OF ANY ALARM VALVE. | | | | | | NO INDICATION OF ANY SPARE SPRINKLER | | | HEADS OR WRENCH PLANNED FOR THE NEW | | | INSTALLATION. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|