Plan Review Notes
Plan Review Notes For Permit 02090764
Permit Number 02090764
Review Stop E
Sequence Number 2
Notes
Date Text
2002-11-25 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION MAKE NECESSARY REVISIONS
 AND SUBMIT FOR REVIEW BEFORE CALLING
 ANY ELECTRICAL INSPECTIONS.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} THE GROUNDING ELECTRODE CONDUCTOR IS
 INCORRECTY SIZED FOR THE SERVICE
 CONDUCTORS PER 250-66.ALSO THE SYSTEM
 IS NOT IN COMPLIANCE WITH 250-50 NEC.
  
 3} SHEET "A-1" SHOWS EXISTING SERVICE TO
 REMAIN,AND ALSO SHOWS "NEW SERVICE ON
 REAR WALL",PLEASE CLARIFY.
  
 4} THE PLAN INDICATES THE SERVICE FROM
 FPL TO THE METER BEING 400 AMP/3 PHASE,
 PLEASE VERIFY SIZE AND RATING OF THE
 SERVICE.
  
 5} THE RISER DIAGRAM MUST SHOW
 COMPLIANCE WITH 225-32 &
 250-32(B)(1).ALSO NOTE 230-70(A) CWPB
 AMMENDMENTS FOR DISCONNECT
 LOCATION,LOCATE SAME ON PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392