| Plan Review Notes For Permit 02090764 |
| Permit Number |
02090764 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-11-25 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION MAKE NECESSARY REVISIONS | | | AND SUBMIT FOR REVIEW BEFORE CALLING | | | ANY ELECTRICAL INSPECTIONS. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} THE GROUNDING ELECTRODE CONDUCTOR IS | | | INCORRECTY SIZED FOR THE SERVICE | | | CONDUCTORS PER 250-66.ALSO THE SYSTEM | | | IS NOT IN COMPLIANCE WITH 250-50 NEC. | | | | | | 3} SHEET "A-1" SHOWS EXISTING SERVICE TO | | | REMAIN,AND ALSO SHOWS "NEW SERVICE ON | | | REAR WALL",PLEASE CLARIFY. | | | | | | 4} THE PLAN INDICATES THE SERVICE FROM | | | FPL TO THE METER BEING 400 AMP/3 PHASE, | | | PLEASE VERIFY SIZE AND RATING OF THE | | | SERVICE. | | | | | | 5} THE RISER DIAGRAM MUST SHOW | | | COMPLIANCE WITH 225-32 & | | | 250-32(B)(1).ALSO NOTE 230-70(A) CWPB | | | AMMENDMENTS FOR DISCONNECT | | | LOCATION,LOCATE SAME ON PLANS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|