| Plan Review Notes For Permit 02090764 |
| Permit Number |
02090764 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-11-27 00:00:00 | THE PREVIOUSLY REQUESTED INFORMATION FOR | | | THE BUILT UP BEAMS HAS NOT BEEN | | | PROVIDED.SEE FBC 104.2 | | | | | | THE PREVIOUSLY REQUESTED CALCULATIONS | | | FOR THE SHEARWALLS HAS NOT BEEN | | | PROVIDED.THE STRUCTURAL PLANS DECLARE | | | WIND DESIGN TO 110 MPH.WEST PALM BEACH | | | IS IN 140 MPH WIND ZONE. NOTE IF FBC | | | 1606.2, ASCE 7-98 SIMPLIFIED,OR | | | ANALYTICAL METHOD OF WIND DESIGN WAS | | | USED FOR THIS BUILDING. | | | | | | HOW WERE THE PRESSURES OF -36 +48 FOR | | | THE WINDOWS DETERMINED?HOW WILL THE | | | STRUCTURAL ADEQUACY OF THE RELOCATED | | | WINDOWS BE DEMONSTRATED? | | | | | | PRESSURES AND ZONES FOR THE ROOF ARE NOT | | | PROVIDED. (COMPONENTS AND CLADDING) | | | | | | THE SHEET STAMPED FOR THE IMPACT FEES | | | MUST BE INCLUDED WITH THE PERMIT SET. | | | | | | THE VENT AREA FOR THE ATTIC IS NOT | | | ESTABLISHED, NOTES SUCH AS "MATCH | | | EXISTING WITH ADDITIONAL VENTS IF | | | NECESSARY" AND QUOTING THE CODE ARE NOT | | | ACCEPTABLE SUBSTITUTES FOR SPECIFIC | | | DESIGN INFORMATION. | | | SEE FBC 104.2 |
|