2002-11-27 00:00:00THE PREVIOUSLY REQUESTED INFORMATION FOR
 THE BUILT UP BEAMS HAS NOT BEEN
 PROVIDED.SEE FBC 104.2
  
 THE PREVIOUSLY REQUESTED CALCULATIONS
 FOR THE SHEARWALLS HAS NOT BEEN
 PROVIDED.THE STRUCTURAL PLANS DECLARE
 WIND DESIGN TO 110 MPH.WEST PALM BEACH
 IS IN 140 MPH WIND ZONE. NOTE IF FBC
 1606.2, ASCE 7-98 SIMPLIFIED,OR
 ANALYTICAL METHOD OF WIND DESIGN WAS
 USED FOR THIS BUILDING.
  
 HOW WERE THE PRESSURES OF -36 +48 FOR
 THE WINDOWS DETERMINED?HOW WILL THE
 STRUCTURAL ADEQUACY OF THE RELOCATED
 WINDOWS BE DEMONSTRATED?
  
 PRESSURES AND ZONES FOR THE ROOF ARE NOT
 PROVIDED. (COMPONENTS AND CLADDING)
  
 THE SHEET STAMPED FOR THE IMPACT FEES
 MUST BE INCLUDED WITH THE PERMIT SET.
  
 THE VENT AREA FOR THE ATTIC IS NOT
 ESTABLISHED, NOTES SUCH AS "MATCH
 EXISTING WITH ADDITIONAL VENTS IF
 NECESSARY" AND QUOTING THE CODE ARE NOT
 ACCEPTABLE SUBSTITUTES FOR SPECIFIC
 DESIGN INFORMATION.
 SEE FBC 104.2