| 2002-10-11 00:00:00 | BUILDING PLAN REVIEW |
| | ******PROVISO******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | --PROVISO-- |
| | FBC 1007.5A HANDRAIL SHALL BE PROVIDED |
| | BETWEEN 34" AND 38" ABOVE THE LEADING |
| | EDGE OF THE TREADS ON THE NEW STAIRWAY. |
| | |
| | --PROVISO-- |
| | FBC 2405.2IF THE NEW SHOWER ENCLOSURE |
| | IS TO INCORPORATE GLASS, IT IS REQUIRED |
| | TO BE SAFETY GLASS SATISFYING THE |
| | REQUIREMENTS OF THE CONSUMER PRODUCT |
| | SAFETY COMMISSION 16, CODE OF FEDERAL |
| | REGULATIONS, PART 1201 (CPSC 16-CFR, |
| | PART 1201). |
| | |
| | --PROVISO-- |
| | FBC 1606.1.4BEFORE BUCK INSPECTION, A |
| | PRODUCT APPROVAL SHALL BE SUBMITTED FOR |
| | THE NEW FRENCH DOORS. |
| | |
| | --PROVISO-- |
| | FBC 3401.7.2.4REPLACEMENT WINDOWS AND |
| | DOORS INSTALLED IN EXISTING BUILDINGS |
| | SHALL COMPLY WITH FBC 2001.AS THE |
| | PROPOSED WINDOWS ARE NOT IMPACT |
| | RESISTANT, IMPACT PROTECTION SHUTTERS |
| | SHALL BE INSTALLED AS REQUIRED BY THE |
| | SUBMITTED PRODUCT APPROVALS.A SEPARATE |
| | PERMIT APPLICATION (TO INCLUDE AN |
| | INSTALLATION SCHEDULE) WILL BE REQUIRED |
| | FOR THE SHUTTERS. |
| | |
| | --PROVISO-- |
| | OUTSWING ALUMINUM CASEMENT WINDOW |
| | PRODUCT APPROVAL NOA# 01-0329.03.THE |
| | DRAWING SHEETS (IN PARTICULAR, SHEETS |
| | 6 THRO' 10 OF 12) HAVE BEEN FAXED AND |
| | COPIED, AND CANNOT BE READ.SUBMIT TWO |
| | LEGIBLE COPIES BEFORE BUCK INSPECTION. |
| | |
| | --PROVISO-- |
| | RECTANGULAR ALUMINUM FIXED WINDOW |
| | PRODUCT APPROVAL NOA# 01-0209.11.THE |
| | 'PRODUCT DESCRIPTION'(SHEET 2, ITEM 2.1) |
| | STATES THAT THE WINDOW SHALL BE IN |
| | STRICT COMPLIANCE WITH DRAWING NO 97-001 |
| | THIS WAS NOT SUBMITTED WITH THE PRODUCT |
| | APPROVAL. BEFORE BUCK INSPECTION, SUBMIT |
| | TWO COPIES OF THE STAMPED 'PRODUCT |
| | APPROVED' DRAWING NO. 97-001. |
| | |
| | --PROVISO-- |
| | PRODUCT APPROVAL SUBMITTAL FORM FOR |
| | KINCO LIMITED ALUMINUM SINGLE HUNG |
| | WINDOW.BEFORE BUCK INSPECTION, THIS |
| | FORM SHALL BE MADE 'SITE SPECIFIC' BY |
| | HAVING ITEM 10.0 COMPLETED BY THE DESIGN |
| | PROFESSIONAL OF RECORD.AS THE BEEMS |
| | CONSTRUCTION PLAN HAS NOT BEEN PREPARED |
| | BY A REGISTERED ARCHITECT OR |
| | PROFESSIONAL ENGINEER, ITEM 10.0 MAY BE |
| | COMPLETED BY THE PROJECT ENGINEER |
| | (CAMERON MILLER, P.E) OR BY THE ENGINEER |
| | WHO COMPLETED THE CERTIFICATION IN |
| | ITEM 9.0 (HUMAYOU FAROOQ, P.E.). |