| Notes |
| Date |
Text |
| 2003-04-07 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE W/ SUBMITTED PANEL | | | SCHEDULE. CIRCUITING FOR EM/EXT LTS | | | 700-12E | | | 2)NOTE: PLEASE SEE PANEL SCHEDULE, SHOWS | | | ONLY ONE CIRCUIT FOR OFFICE RECEPTS?? | | | 220-13 | | | | | | 3)NOTE: PLEASE CLARIFY 100/20 SHOWN | | | ON PANEL SCHEDULE. | | | | | | 4)NOTE: PLEASE SEE PANEL SCH. SHOWS A | | | 200A 2/P, ? FOR? | | | CIRCUIT #4 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | [email protected] |
|