| Plan Review Notes For Permit 02090718 |
| Permit Number |
02090718 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-12-27 00:00:00 | PROVISO:MECHANICAL PERMIT 02090802 | | | | | | RETURN AIR DUCTS OR TRANSFER GRILLES | | | REQUIRED FROM ALL "OFFICE" AREAS. | | | | | | CONDENSATE SHALL DISCHARGE A MINIMUM | | | OF 12" AWAY FROMT THE BUILDING STRUCTURE | | | AS PER 2001 FBC 1503.4.4. | | | | | | EXHAUST FROM BATHROOMS SHALL NOT | | | BE DIRECTED ONTO WALKWAYS AS PER 2001 | | | FBC(M) 401.5.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|