| Plan Review Notes For Permit 02090718 |
| Permit Number |
02090718 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-07 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE FIRE REVIEW COMMENTS | | | FOR EXIT AND EMGERGENCY LTS. 700-12 | | | | | | 2)NOTE: PLEASE PROVIDE CIRCUTIING ON | | | PLANS AND CORRELATE W/ SUBMITTED PANEL | | | SCHEDULE. | | | | | | 3)NOTE: PLEASE CLARIFY EQUIPMENT GROUND- | | | -ING METHOD BETWEEN MAIN AND SUB-PANEL. | | | SIZE PER 250-122 | | | | | | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS, PANELS, BRKRS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT. 110-9 | | | | | | 5)NOTE: PLEASE CLARIFY SIZE FOR SERVICE | | | ENTRANCE CONDUCTORS. SHOWN AS 3-3/10`S | | | ? 310-16 | | | | | | 6)NOTE: PLEASE SHOW RECEPT FOR A/C UNIT | | | 210-63. | | | | | | 7)NOTE: PLEASE NOTE ALL CONTINUOUS LOADS | | | ARE TO BE SHOWN AT 125%. | | | 215-3,230-42 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELETRICAL PLAN REVIEW | | | 561-659-8096 EX8372 |
|