Plan Review Notes
Plan Review Notes For Permit 02090697
Permit Number 02090697
Review Stop P
Sequence Number 2
Notes
Date Text
2003-03-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) WATER HEATER P/T FROM 2ND AND 3RD
 FLOORS SHALL DRAIN THRU CEILING OF THE
 FIRST FLOOR AND STUB OUT 6" ABOVE GRADE.
 HEATER PANS ARE NOT APPROVED INDIRECT
 WASTE RECEPTORS. FIRST FLOOR P/T CAN
 DRAIN TO FLOOR.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377