Plan Review Notes For Permit 02090697
Permit Number 02090697
Review Stop M
Sequence Number 2
Notes
Date Text
2003-02-19 00:00:00DENIED:
 ITEMS NOT ADDRESSED ON REVIEW BY HAROLD
 MOSERR DATED 10/08/02.
 1.VERIFY OUTSIDE AIR REQUIREMENTS.
 INDICATE CALCULATIONS FOR NATURAL
 (2001 FBC(M) 402.2) OR MECHANICAL (2001
 FBC(M) TABLE 403.3).
  
 2.DUCTS EXTENDING MORE THAN 1 FLOOR
 ARE REQUIRED TO BE ENCLOSED BY A SHAFT
 ENCLOSURE AS PER 2001 FBC(M) 607.4.
 PROVIDE DETAIL OF UL SHAFT ASSEMBLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.