| Plan Review Notes For Permit 02090697 |
| Permit Number |
02090697 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-03-13 00:00:00 | 1) SOME PLAN REVIEW COMMENTS HAVE NOT | | | BEEN PROPERLY ADDRESSED. | | | | | | 2) EXIT SIGNS REQUIRED AT FIRST FLOOR | | | LEVEL. | | | | | | 3) NFPA 13 SYSTEMS MUST BE USED WHEN | | | CODE REQUIRMENTS HAVE BEEN ALTERED. NFPA | | | 13R SYSTEMS SHALL NOT BE USED. | | | | | | 4) PLEASE INDICATE LOCATIONS OF FDC'S IN | | | RELATION TO THE FIRE HYDRANTS. FDC'S SHA | | | SHALL NOT EXCEED 150 FEET TO A FIRE | | | HYDRANT. | | | | | | 5) IT APPEARS THAT ADDITIONAL FIRE | | | HYDRANTS ARE REQUIRED ON THE SITE PLAN. | | | BETTER PLACEMENT WITH ADDITIONAL FIRE | | | HYDRANTS WOULD APPEARS TO BE PROPER. | | | | | | NATE MCCRAY, CAPTAIN | | | 659-8096, EXT 8497 | | | 835-2910 |
|