| Plan Review Notes For Permit 02090697 |
| Permit Number |
02090697 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-05 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) SHTS P-U1, P-U2, P-U3, & P-U4 WATER | | | RISER DIAGRAMS, WATER HAMMER ARRESTORS | | | AT WASHMACHINES TO BE LOCATED NEAR FIX- | | | TURES IN AN "EFFECTIVE RANGE" NOT AT THE | | | TOP OF THE DROP AS SHOWN. | | | 2) SHT P-T1.1 CLEAN OUT REQUIRED IN THE | | | BREEZE WAY TO THE LEFT OF WHERE BLDG. | | | DRAIN ENTERS THE BLDG. SEC 708.3.1 | | | 3) SHT P-T1.3 SANITARY RISER DIAGRAM, | | | SEE PREVIOUS COMMENT (#2). | | | 4) SHT PD-1 WATER HEATER PAN DRAIN & T/P | | | RELIEF RISERS, T/P RELIEF LINE SHALL NOT | | | BE TRAPPED. SEC 504.7.1 | | | 5) SHT PD-1 PLUMBING GENERAL NOTES #6, | | | DIELECTRIC UNIONS ARE NOT APPROVED FOR | | | WATER. PLEASE DELETE REFERENCE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|