Plan Review Notes
Plan Review Notes For Permit 02090696
Permit Number 02090696
Review Stop B
Sequence Number 3
Notes
Date Text
2003-04-15 00:00:00THIRD PAID PLAN REVIEW NOT A PERMIT
 APPLICATION.
  
 THE FIRE PROTECTION PLANS MUST ACCOMPANY
 THE PERMIT PLANS. SEE FBC 104.3.1.1 #5.
  
 THE CONSTUCTION BOARD OF ADJUSTMENT AND
 APPEALS CASE #1225 HEARD 1/8/03 GRANTED
 A VARIANCE TO THE 50% LONG SIDE OPEN
 BALCONY REQUIREMENT OF FBC 1014.1.1.
  
 FIRE SPRINKLERS INSTALLED AS A CODE
 REQUIREMENT MUST BE A NFPA 13 SYSTEM.
 SEE FBC 903.2.
  
 THE EXITS DO NOT MEET THE 1/2 DIAGONAL
 DISTANCE SEPARATION REQUIREMENTS OF FBC
 1006.2.2.