| Plan Review Notes For Permit 02090696 |
| Permit Number |
02090696 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-02-19 00:00:00 | DENIED: | | | ITEMS NOT ADDRESSED ON REVIEW BY HAROLD | | | MOSER DATAED 10/08/02. | | | 1.VERIFY OUTSIDE AIR REQUIREMENTS. | | | INDICATE CALCULATIONS FOR NATURAL | | | (2001 FBC(M) 402.2) OR MECHANICAL (2001 | | | FBC(M) TABLE 403.3). | | | | | | 2.DUCTS EXTENDING MORE THAN 1 FLOOR | | | ARE REQUIRED TO BE ENCLOSED BY A SHAFT | | | ENCLOSURE AS PER 2001 FBC(M) 607.4. | | | PROVIDE DETAIL OF UL SHAFT ASSEMBLY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|