Plan Review Notes
Plan Review Notes For Permit 02090696
Permit Number 02090696
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2003-03-06 00:00:001) SOME PLAN REVIEW COMMENTS HAVE
 NOT BEEN PROPERLY ADDRESSED.
  
 2) EXIT SIGNS REQUIRED AT FIRST FLOOR
 LEVEL.
  
 3) IT APPEARS THAT ADDITIONAL FIRE
 HYDRANTS ARE REQUIRED ON THE SITE PLAN.
 BETTER PLACEMENT WITH ADDITIONAL FIRE
 HYDRANTS WOULD APPEAR TO BE PROPER.
  
 4) PLEASE INDICATE LOCATIONS OF FDC'S
 IN RELATION TO THE FIRE HYDRANTS. FDC'S
 SHALL NOT EXCEED 150 FEET TO A FIRE
 HYDRANT.
  
 5) NFPA 13R SYSTEMS SHALL NOT BE USED
 WHEN CODE REQUIREMENTS HAVE BEEN
 ALTERED. NFPA 13 SYSTEMS MUST BE USED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910