| Plan Review Notes For Permit 02090696 |
| Permit Number |
02090696 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-05 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) SHTS P-U1, P-U2, P-U3, P-U4, P-U5, & | | | P-U6, WATER RISER DIAGRAMS, WATER HAMMER | | | ARRESTORS AT WASH MACHINES SHALL BE LO- | | | CATED NEAR THE FIXTURES IN AN "EFFECTIVE | | | RANGE" NOT AT THE TOP OF DROPS AS SHOWN. | | | PDI-WH 201 AND MANUFACTURE INSTALLATION | | | INSTRUCTIONS. 604.9 | | | 2) SHT P-T3.1 CLEAN OUTS SHALL BE RE- | | | QUIRED IN EACH BREEZE WAY. 100' MAX BE- | | | TWEEN C/O'S SEC 708.3.1 | | | 3) SHT P-T3.3 SANITARY RISER DIAGRAM, | | | SEE PREVIOUS COMMENT. (#2) | | | 4) SHT PD-1 WATER HEATER DRAIN & P/T RE- | | | LIEF RISERS. T/P LINE SHALL NOT BE TRAP- | | | PED SEC 504.7.1 | | | 5) SHT PD-1 PLUMBING GENERAL NOTES #6, | | | DIELECTRIC UNIONS NOT APPROVED FOR WATER | | | LINES. PLEASE DELETE REFERENCE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|