Plan Review Notes
Plan Review Notes For Permit 02090696
Permit Number 02090696
Review Stop P
Sequence Number 1
Notes
Date Text
2002-10-05 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHTS P-U1, P-U2, P-U3, P-U4, P-U5, &
 P-U6, WATER RISER DIAGRAMS, WATER HAMMER
 ARRESTORS AT WASH MACHINES SHALL BE LO-
 CATED NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT AT THE TOP OF DROPS AS SHOWN.
 PDI-WH 201 AND MANUFACTURE INSTALLATION
 INSTRUCTIONS. 604.9
 2) SHT P-T3.1 CLEAN OUTS SHALL BE RE-
 QUIRED IN EACH BREEZE WAY. 100' MAX BE-
 TWEEN C/O'S SEC 708.3.1
 3) SHT P-T3.3 SANITARY RISER DIAGRAM,
 SEE PREVIOUS COMMENT. (#2)
 4) SHT PD-1 WATER HEATER DRAIN & P/T RE-
 LIEF RISERS. T/P LINE SHALL NOT BE TRAP-
 PED SEC 504.7.1
 5) SHT PD-1 PLUMBING GENERAL NOTES #6,
 DIELECTRIC UNIONS NOT APPROVED FOR WATER
 LINES. PLEASE DELETE REFERENCE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377