| 2002-10-08 00:00:00 | ****************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE NOTE, AS PER NOTE #7 ON |
| | E-U1. THE LOCK OFF DEVICE MUST BE |
| | A PART OF THE BREAKER. PLEASE NOTE THE |
| | TYPE OF LOCK OFF DEVICE CHOSEN NEEDS TO |
| | BE REVIEWED BY THE CITY OF WEST PALM |
| | BEACH BEFORE INSTALLATION. PLEASE NOTE, |
| | MOST OF THE "SNAP ON" DEVICES ARE NOT |
| | PERMITTED TO BE USED AND A MEANS OF DISC |
| | IS REQ`D. PLEASE NOTE ON PLANS. |
| | |
| | 2)NOTE: PLEASE SHOW REQ`MENTS FOR FAIR |
| | HOUSING ACT. FHAR 24 CFR 100.205. |
| | |
| | 3)NOTE: PLEASE NOTE CLEARENCE FOR CLOSET |
| | LIGHT INSTALLATION PER 410-8. |
| | |
| | 4)NOTE: PLEASE CLARIFY LOCATION OF |
| | SERVICE RECEPT FOR A/C COND UNIT. 210-63 |
| | |
| | 5)NOTE: PLEASE SEE 230-72 FOR GROUPING |
| | OF MAINS . PLEASE NOTE A SHUNT TRIP |
| | MAY NOT BE USED FOR GROUPING OF MAINS. |
| | PLEASE SEE 230-76,230-79. |
| | PLEASE CLARIFY HOW THIS MEETS 230-2 |
| | AND THE ABOVE. |
| | |
| | 6)NOTE: PLEASE CLARIFY METHOD OF EQUIP- |
| | -MENT GROUNDIG BETWEEN METER/MAIN AND |
| | HOUSE PANEL? SIZE PER 250-122 |
| | |
| | 7)NOTE: PLEASE SHOW INDICATION OF MAINS |
| | FOR APT UNITS ON RISER DIAGRAM. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |