2002-10-02 00:00:00PAID PLAN REVIEW NOT A PERMIT
 APPLICATION.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO THE
 COUNTY, THE PERMIT PLANS STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 ON PROJECTS OF THIS SCOPE THE BUILDING
 OFFICIAL WILL REQUIRE A RESIDENT
 INSPECTOR.CONTACT DON NEELY,
 561-659-8096 X 8333, FOR MORE
 INFORMATION.
  
 AT TIME OF PERMIT APPLICATION, IF THE
 TEST AND OR NOTICE OF ACCEPTANCE
 REPORTS, FOR THE WINDOWS, DOORS AND
 ROOF COVERING ARE NOT INCLUDED, SEPARATE
 PERMITS AND FEES WILL BE REQUIRED.
  
 SHEET AS-1 DECLARES 13,864 SQUARE FEET
 FOR A TYPE III BUILDING AND SHEET
 A-T3.1 16,016.PLEASE CLARIFY.SEE
 FBC 202, "AREA, BUILDING"
  
 THE DETAIL 17/A-DT2 DOES NOT AGREE WITH
 FBC FIGURE 709.5.1C FOR THE ONE HOUR
 FIRE RATED COLUMN.
  
 THE NOTES ON SHEET A-DT1 DECLARE THE USE
 OF HURRICANE SHUTTERS.SEE THE
 BUILDING OFFICIAL'S POLICY STATEMENT
 ATTACHED.HURRICANE MISSILE IMPACT
 RESISTANT GLAZING IS REQUIRED
 THROUGHOUT.
  
 THE DROPPED SOFFIT DETAIL 14/ADT-2 NEEDS
 SPECIFIC FRAMING AND FASTENER DETAILS.
 SEE FBC 104.2.
  
 NOTE #3 ON SHEET SD-4 DECLARES DESIGN TO
 THE 1997 SBC AND 110 MPH.PLEASE
 REVISE AND INSURE COMPLIANCE WITH FBC
 1606 FOR 140 MPH WIND ZONE.
  
 SHOW THE FIRE PROTECTION DESIGN
 INFORMATION.SEE FBC 104.2.
  
 THE EXIT STAIRS ARE REQUIRED TO BE
 ENCLOSED IN FIRE RATED CONSTRUCTION IN
 ACCORDANCE WITH FBC 1006.1 OR COMPLY
 WITH FBC 1006.2 FOR EXTERIOR STAIRS.
 AS DEPICTED ON THESE PLANS THEY COMPLY
 WITH NEITHER.
  
 THE THIRD FLOOR REQUIRES TWO INDEPENDENT
 MEANS OF EGRESS.SEE FBC 1004.2.1.
  
 SHEET SD-5 HAS INCORRECTLY LABELED
 ROOF CORNER ZONES.