| Date |
Text |
| 2002-10-02 00:00:00 | PAID PLAN REVIEW NOT A PERMIT |
| | APPLICATION. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO THE |
| | COUNTY, THE PERMIT PLANS STAMPED BY |
| | THAT OFFICE AND A COPY OF THE PAID |
| | RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION.CALL 561-233-5025 FOR |
| | MORE INFORMATION. |
| | |
| | ON PROJECTS OF THIS SCOPE THE BUILDING |
| | OFFICIAL WILL REQUIRE A RESIDENT |
| | INSPECTOR.CONTACT DON NEELY, |
| | 561-659-8096 X 8333, FOR MORE |
| | INFORMATION. |
| | |
| | AT TIME OF PERMIT APPLICATION, IF THE |
| | TEST AND OR NOTICE OF ACCEPTANCE |
| | REPORTS, FOR THE WINDOWS, DOORS AND |
| | ROOF COVERING ARE NOT INCLUDED, SEPARATE |
| | PERMITS AND FEES WILL BE REQUIRED. |
| | |
| | SHEET AS-1 DECLARES 13,864 SQUARE FEET |
| | FOR A TYPE III BUILDING AND SHEET |
| | A-T3.1 16,016.PLEASE CLARIFY.SEE |
| | FBC 202, "AREA, BUILDING" |
| | |
| | THE DETAIL 17/A-DT2 DOES NOT AGREE WITH |
| | FBC FIGURE 709.5.1C FOR THE ONE HOUR |
| | FIRE RATED COLUMN. |
| | |
| | THE NOTES ON SHEET A-DT1 DECLARE THE USE |
| | OF HURRICANE SHUTTERS.SEE THE |
| | BUILDING OFFICIAL'S POLICY STATEMENT |
| | ATTACHED.HURRICANE MISSILE IMPACT |
| | RESISTANT GLAZING IS REQUIRED |
| | THROUGHOUT. |
| | |
| | THE DROPPED SOFFIT DETAIL 14/ADT-2 NEEDS |
| | SPECIFIC FRAMING AND FASTENER DETAILS. |
| | SEE FBC 104.2. |
| | |
| | NOTE #3 ON SHEET SD-4 DECLARES DESIGN TO |
| | THE 1997 SBC AND 110 MPH.PLEASE |
| | REVISE AND INSURE COMPLIANCE WITH FBC |
| | 1606 FOR 140 MPH WIND ZONE. |
| | |
| | SHOW THE FIRE PROTECTION DESIGN |
| | INFORMATION.SEE FBC 104.2. |
| | |
| | THE EXIT STAIRS ARE REQUIRED TO BE |
| | ENCLOSED IN FIRE RATED CONSTRUCTION IN |
| | ACCORDANCE WITH FBC 1006.1 OR COMPLY |
| | WITH FBC 1006.2 FOR EXTERIOR STAIRS. |
| | AS DEPICTED ON THESE PLANS THEY COMPLY |
| | WITH NEITHER. |
| | |
| | THE THIRD FLOOR REQUIRES TWO INDEPENDENT |
| | MEANS OF EGRESS.SEE FBC 1004.2.1. |
| | |
| | SHEET SD-5 HAS INCORRECTLY LABELED |
| | ROOF CORNER ZONES. |