Plan Review Notes
Plan Review Notes For Permit 02090695
Permit Number 02090695
Review Stop B
Sequence Number 2
Notes
Date Text
2003-02-13 00:00:00PAID PLAN REVIEW NOT A PERMIT
 APPLICATION.
  
 THE COMMENTS PROVIDED IN THE 10/02/02
 LIST REGARDING IMPACT FEES, RESIDENT
 INSPECTOR, PRODUCT REPORTS, ETC. ARE
 THE SAME AND STILL APPLICABLE.
  
 SHEET SD4 STILL CONTAINS DESIGN
 INFORMTION AS BEING 1997 SBC AND 110
 MPH.SD5 MAKES REFERENCE TO THE HVHZ
 AND FBC 1606.2.THE CITY OF WEST PALM
 BEACH IS UNDER THE 2001 FLORIDA
 BUILDING CODE AND IS IN THE 140 MPH
 WIND ZONE.CLEARLY NOTE IF ASCE 7-98
 CHAPTER 6 OR FBC 1606.2 WAS USED FOR
 THE DESIGN, IN ADDITION OR IN PLACE OF
 THE SEVERAL CODES AND STANDARDS CITED
 ON THE PLANS.
  
 THERE ARE STILL TWO INDEPENDENT EXITS
 REQUIRED BY FBC 1004.2.1 FOR THE SECOND
 AND THIRD LEVELS.
  
 THE EXIT CONFIGURATION SHOWN DOES NOT
 COMPLY WITH FBC 1006.1 FOR ENCLOSED
 STAIRS OR 1006.2 FOR EXTERIOR STAIRS.
  
 THESE COMMENTS APPLY TO BUILDINGS TYPE
 I, II, AND III, AND ARE NOT REPEATED ON
 THOSE PLAN REVIEWS NUMBERS 02090696 AND
 02090697.