| Plan Review Notes For Permit 02090695 |
| Permit Number |
02090695 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-12 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) SHTS P-U3, P-U4, P-U5, & P-U6 WATER | | | RISER DIAGRAMS, WATER HAMMER ARRESTORS | | | AT WASH MACHINES TO LOCATED NEAR FIX- | | | TURES IN AN "EFFECTIVE RANGE" NOT AT THE | | | TOP OF THE DROP AS SHOWN. | | | 2) SHT P-T2.1 CLEAN OUT REQUIRED IN THE | | | BREEZE WAYS. SEC 708.3.1 - 100' MAX BE- | | | TWEEN CLEANOUTS. | | | 3) SHT P-T2.3 CLEAN OUTS REQUIRED IN | | | SANITARY RISER DIAGRAM. SEE COMMENT #2 | | | 4) SHT PD-1 WATER HEATER PAN DRAIN & T/P | | | RELIEF RISERS, T/P RELIEF LINE SHALL NOT | | | BE TRAPPED. SEC 504.7.1 | | | 5) SHT PD-1 PLUMBING GENERAL NOTES #6, | | | DIELECTRIC UNIONS ARE NOT APPROVED FOR | | | WATER. PLEASE DELETE REFERENCE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|