| Plan Review Notes For Permit 02090695 |
| Permit Number |
02090695 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-08 00:00:00 | PLAN DENIED | | | 1) VARIFY TYPE OF VENTILATION USED FOR | | | FRESH AIR.SECTION 402 NATURAL OR | | | MECHANICAL SECTION 403 FBC.2001 | | | 2) NEED CALCULATIONS FOR TYPE OF | | | VEVTILATION USED | | | 3) NEED MANUFACTURERS INSTALLATION ON | | | CLOTHES DRYER | | | 4) REFER TO SECTION 306.1.1 CLEARANCE | | | AROUND AIRHANDLER | | | 5) CAN NOT RUN DRYER VENT AND BATHROOM | | | EXHAUST IN SAME CHASE | | | 6) REFER TO SECTION 401.6 BATHROOM | | | EXHAUST WALL CAP MUST HAVE SCREEN. | | | BACKDRAFT DAMPER ON FAN ONLEY | | | 7) NEED ENERGY CALCS & MANUAL (J) | | | PLAN REVIEW BY HAROLD MOSER | | | (561)659-8096 EXT.8390 |
|