Plan Review Notes
Plan Review Notes For Permit 02090695
Permit Number 02090695
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-10-04 00:00:001) PLEASE PROVIDE A LIFE SAFETY PLAN FOR
 THE BUILDING. PLEASE INDICATE EXIT
 SEPARATIONS, TRAVEL DISTANCES, ETC.
  
 2) NO FIRE SPRINKLER PLANS OR HYDRAULIC
 CALCULATIONS PROVIDED WITH PLANS.
  
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM.
  
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM.
  
 5) WHAT PROVISIONS WILL BE MADE FOR FIRE
 AND PARAMEDICAL ACCESS THRU THE SECURITY
 GATES WHEN NORMAL POWER IS PRESENT. THIS
 OFFICE USUALLY REQUIRES A KNOX-BOX KEY
 SWITCH.
  
 6) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.