| Notes |
| Date |
Text |
| 2002-09-17 00:00:00 | 1) FIRE ALARM NOTES INDICATES CLASS B, | | | STYLE C. ONLY CLASS A, STYLE D IS | | | PERMITTED. | | | | | | 2) PLEASE INDICATE LOCATIONS OF | | | EMERGENCY LIGHT FIXTURES IN HALLWAY. | | | | | | 3) DOES THE EXISTING SMOKE DETECTOR IN | | | THE ELEVATOR LOBBY PROVIDE PHASE ONE | | | PHASE TWO ELEVATOR RECALL. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|