| Date |
Text |
| 2003-01-29 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) FROM PREVIOUS REVIEW: PLEASE SHOW |
| | COMPLIANCE WITH THE FAIR HOUSING ACT |
| | REQUIREMENTS 1 THRU 7. INDICATE SPECI- |
| | FICATION "A" OR "B" FOR EACH BATHROOM IN |
| | UNITS 1,2,4, & 5. SHOW BACKING AND CLEAR |
| | FLOOR SPACE FOR REQUIRED FIXTURES. |
| | 2) FROM PRIVIOUS REVIEW: SHT 2 OF 3, IN- |
| | DICATE LOCATION OF PRIMARY AND SECONDARY |
| | ROOF DRAINS. INDICATE SQUARE FOOTAGE OF |
| | ROOF BEING DRAINED INCLUDING 1/2 AREA |
| | OF ALL VERTICAL WALLS INCLUDING PARAPET |
| | WALLS. SHOW SIZE OF PRIMARY AND SECOND- |
| | ARY ROOF DRAINS. |
| | 3) SHT 2 0F 3 SANITARY RISER DIAGRAM |
| | DOES NOT MEET CODE. UNIT #5 LAV AND KIT. |
| | SINK SHALL NOT BE ON SAME RISER, (DIFF- |
| | ERENT WALLS. PLEASE MOVE LAV TO WHERE |
| | INDICATED). 2ND FLOOR UNIT #6 SHALL TIE |
| | IN DOWNSTREAM OF BATHROOM FOR UNIT #5. |
| | FLOOR DRAIN REQUIRED FOR LAUNDRY ROOM. |
| | KITCHEN FOR UNIT #1 SHALL BE LOCATED |
| | NEAR BATHROOM WHERE DRY HORIZONTAL VENT |
| | IS NOT LOCATED. KITCHEN FOR UNIT #6 IS |
| | NOT SHOWN AND SHALL BE SHOWN AS ON THE |
| | 2ND FLOOR. |
| | 4) SHT 2 OF 3, LAV FOR UNIT #6 IS NOT |
| | SHOWN ON FLOOR PLAN. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |