| Plan Review Notes For Permit 02090646 |
| Permit Number |
02090646 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-02-10 00:00:00 | DENIED: | | | | | | PROVIDE PLANS INDICATING DUCT SIZE, | | | MATERIAL, AND LAYOUT. | | | | | | PROVIDE HVAC EQUIPMENT INFORMATION. | | | | | | 2001 FBC(M) 402.2 - NATURAL VENTILATION | | | FOR OUTSIDE AIR REQUIRMENT. SHOW | | | COMPLIANCE FOR THE MINIMUM OPENABLE AREA | | | TO THE OUTDOORS. (4 PERCENT OF THE FLOOR | | | AREA BEING VENTILATED) OR TABLE 403.3 | | | FOR MECHANICAL VENTILATION. | | | | | | (ENERGY & MANUAL J CALCS SUBMITTED) | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|