| Plan Review Notes For Permit 02090643 |
| Permit Number |
02090643 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-01-30 00:00:00 | *************** UNSAT ************** | | | | | | PLEASE NOTE, THERE ARE MANY ITEMS | | | FROM FIRST TWO REVIEWS NOT DONE. | | | PLEASE SEE ATTACHED LETTER FOR FS 553-80 | | | | | | 1)NOTE: PLANS HAVE BEEN REVISED NOW | | | SHOWING LAUNDRY CIRCUIT, HOWEVER PER | | | 210-11-C2 MUST BE A MIN 1500KW. | | | 210-52 | | | | | | 2)NOTE: PLANS STILL MISSING OUTLETS | | | LISTED PER 210-12 ON PANEL SCHEDULE. | | | ALSO 210-52,210-52E | | | | | | 3)NOTE: PLEASE SEE ELECTRICAL NOTES | | | MENTIONING A/C UNIT DISC'S TO BE 50A`S?? | | | PLEASE CLARIFY WHERE A/C'S UNIT ARE | | | SHOWN ON PLANS?? | | | | | | PLEASE SEE ANY PREVIOUS NOTES. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | PLEASE ALSO NOTE A 4X FEE WILL BE | | | ACCESSED IF NOTES ARE NOT ADDRESSED FOR | | | PLAN REVIEW.PER FS 553-80(2)(B) | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|