| Date |
Text |
| 2002-12-05 00:00:00 | *************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE NOTE, REVIEW IS DONE FOR |
| | A COMPLETED SERVICE RISER. PLEASE NOTE, |
| | MISSING AIC RATING FOR NEW SERVICE |
| | EQUIPMENT. MAIN DISC'S , PANELS AND BRKR |
| | -S ALL MUST BE RATED FOR THE AVAILABLE |
| | FAULT CURRNT PER 110-9 |
| | |
| | 2)NOTE: PLEASE NOTE MISSING REQ'D |
| | CIRCUITS PER 210-11C-2 (LAUNDRY) |
| | |
| | 3)NOTE: PLEASE NOTE, WATER HEATERS MAY |
| | NOT BE IN STORAGE/CLOSETS W/ EASILY |
| | IGNITABLE MATERIALS. PLEASE PROVIDE |
| | SEPARATION.422-17 |
| | |
| | 4)NOTE: PLEASE NOTE ITMES FROM FIRST |
| | REVIEW WERE NOT ADDRESSED. 210-52E/ |
| | 210-12 |
| | |
| | PLEASE NOTE, FOOTER STEEL IS SHOWN ON |
| | RISER, PLEASE NOTE, NOT REQ`D ON EXIST- |
| | ING BLDG TO CUT CONCRETE FOR THIS.PLEASE |
| | NOTE HOWEVER, IF SHOWN ON PLANS, THEN IT |
| | WILL BE REQ`D. PLEASE ALSO NOTE |
| | SERVICE CONDUCTORS ARE BEING SHOWN AT |
| | FOUR TIMES LARGER THAN REQ`D PER 310-15 |
| | PLEASE NOTE, THE ABOVE IS JUST A NOTE |
| | AND DOES NOT REFLECT ANY CODE VIOLATIONS |
| | IF CHANGED AT LATER DATE, A REVISION |
| | WILL BE REQ`D. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |