| Plan Review Notes For Permit 02090643 |
| Permit Number |
02090643 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-01 00:00:00 | SHOW THE WIND PRESSURES +/- FOR THE | | | WINDOWS AND ROOF COVERING.SEE FBC | | | 1606.1.7 #7. | | | | | | SHOW THE EXISTING OR PROVIDE NEW FIRE | | | RATED TENANT SEPARATION.SEE FBC 704.3. | | | | | | SHOW THE EXISTING OR PROVIDE A FIRE | | | RATED ENCLOSURE FOR THE INTERIOR STAIRS | | | IN THE EAST BUILDING.SEE FBC 1006.1.1. | | | | | | SHOW THE EXISTING OR PROVIDE NEW, | | | HANDRAILS ON EACH SIDE OF ALL THE | | | STAIRS, IN BOTH BUILDINGS.SEE FBC | | | 1007.5. | | | | | | THE SURVEY SHOWS ONE STAIR ON THE WEST | | | SIDE OF THE WEST BUILDING.THE PLANS | | | SHOW STAIR WAYS ON THE WEST AND EAST | | | SIDES. PLEASE CLARIFY DESIGN INTENT. | | | | | | THE EXTERIOR STAIRS MUST COMPLY WITH | | | FBC 1006.2.2 FOR 3/4 HOUR PROTECTED | | | OPENING EXPOSURE.PLEASE REVISE AS | | | NECESSARY. | | | | | | NOTE CLEARLY THE EMERGENCY ESCAPE AND | | | RESCUE OPENINGS FOR THE SLEEPING ROOMS | | | IN ACCORDANCE WITH FBC 1005.4.1. |
|