| 2002-10-10 00:00:00 | BUILDING DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) THE STRUCTURE IS LOCATED IN AN "A5" |
| | FLOOD ZONE THE MINIMUM ELEVATION IS 7.5 |
| | FEET. AN ELEVATION CERTIFICATE WILL BE |
| | REQUIRED FOR ADDITION. |
| | THE CITY CODE OF WPB REQUIRES ALL NEW |
| | CONSTRUCTION OR SUBSTANTIAL IMPROVEMENT |
| | OF ANY EXISTING RESIDENTIAL STRUCTURE TO |
| | HAVE THE LOWEST FLOOR ELEVATED TO SIX |
| | INCHES ABOVE THE BASE FLOOD ELEVATION. |
| | PLEASE INDICATE THE FLOOR ELEVATIONS ON |
| | THE PLANS OR SURVEY. |
| | |
| | 4)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - EXTERIOR WINDOWS |
| | - EXTERIOR DOORS |
| | |
| | 5) PROVIDE (2) PRODUCT APPROVALS, KEY |
| | PLANS AND INSTALLATION SCHEDULES |
| | INDICATING THE SPECIFIC TYPES OF ANCHORS |
| | TO BE USED FOR STORM PANELS. |
| | |
| | 6) SLEEPING ROOMS ARE REQUIRED TO HAVE |
| | AT LEAST ONE EXTERIOR EMERGENCY ESCAPE |
| | AND RESCUE OPENING, PER FBC 1005.4. THE |
| | NET CLEAR OPENING AREA AND DIMENSIONS |
| | MUST COMPLY WITH FBC SEC.1005.4.4. THE |
| | SECOND FLOOR BEDROOMS DO NOT COMPLY. |
| | |
| | 7) INDICATE ACCESS TO ATTIC SPACE AS |
| | REQUIRED BY FBC SEC. 2309.6. |
| | |
| | 8) PLEASE CLARIFY THE WINDOWS THAT HAVE |
| | BEEN DRAWN IN ON THE PLANS. CHANGES MUST |
| | BE SIGNED AND DATED BY THE DESIGNER OF |
| | RECORD. INDICATE WINDOW SIZES AND TYPES. |
| | |
| | 9) THE ADDITION OF THESE WINDOWS EXCEED |
| | THE PERCENT OF WALL AREA ALLOWED AS |
| | OPENINGS BY TABLE 600 FOR THE FIRST AND |
| | SECOND FLOOR OF THE SOUTH ELEVATION. |
| | |
| | 10) THE NORTH ELEVATION ON SHEET A-3 |
| | SHOWS A WINDOW WITH A "C" DESIGNATION |
| | AND THERE IS NO "C" LISTED IN THE WINDOW |
| | SCHEDULE. PLEASE CLARIFY. |
| | |
| | 11) SHEET A-5 LISTS SLOPE ON BALCONY AS |
| | 1/4" PER FOOT AND TOP CUT OF JOISTS IS |
| | INDICATED TO PROVIDE 1/8" PER FOOT SLOPE |
| | PLEASE CLARIFY. NOTE: 1/4":12 SLOPE IS |
| | REQUIRED FOR MODIFIED ROOFING. |
| | |
| | 12) IF STORM PANELS ARE BEING USED, |
| | PLEASE NOTE ON THE PLANS THAT ADEQUATE |
| | SUBSTRATE WILL BE PROVIDED AT GLAZED |
| | OPENINGS FOR THE ATTACHMENT OF STORM |
| | PANELS. |
| | |
| | 13) FBC SEC. 1909.3 REQUIRES WELDED WIRE |
| | MESH TO BE SUPPORTED AT SPACINGS NOT TO |
| | EXCEED 3 FEET. PLEASE INDICATE THIS ON |
| | PLANS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |