| Plan Review Notes For Permit 02090615 |
| Permit Number |
02090615 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-27 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) PLEASE SHOW EXISTING FLOOR PLAN TO | | | SHOW ALL FIXTURES THAT WILL BE DEMO'ED | | | IS THERE AN EXISTING GREASE LINE? | | | 2) PLEASE SUBMIT A SANITARY AND WATER | | | RISER DIAGRAM. SHOW ALL PIPE SIZES, VENT | | | LINES, WATER HAMMER ARRESTORS ECT. | | | 3) A RPZ BACKFLOW SHALL BE REQUIRED FOR | | | WATER SERVICE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|