| Plan Review Notes For Permit 02090615 |
| Permit Number |
02090615 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-25 00:00:00 | ************ UNSAT ******************* | | | | | | 1)NOTE: PLEASE NOTE ALL CIRCUITING NEEDS | | | TO BE ON PLANS AND CORRELATE WITH THE | | | SUBMITTED PANEL SCHEDULE.215-5 | | | | | | 2)NOTE: PLEASE NOTE SIZING OF OCP FOR | | | AHU. PER 424-3. PLEASE NOTE MIN OF 125% | | | SHOWN AS 2P50 FOR 10KW? | | | | | | 3)NOTE : PLEASE CLARIFY NEW OR EXISTING | | | SIGN CIRCUIT PER 600-5 | | | | | | 4)NOTE: PLEASE NOTE LOADS ON BRKRS ON | | | PANEL SCHEDULE NEED TO CORRELATE WITH | | | MAX OCP. PLEASE NOTE #12 W/ 25 BRKR? | | | #6 W/ 24KW LOAD ON 2P-50 FOR X-RAY DISC. | | | PLEASE NOTE X-RAY DISC IS SHOWN AS 100A | | | ON PLANS?? | | | | | | 5)NOTE: PLEASE NOTE THAT ALL CONTINUOUS | | | LOADS NEED TO BE SHOWN AT 125%. PER | | | 215-3,230-42. | | | | | | 6)NOTE: PLEASE CLARIFY SHOW WINDOW J-BOX | | | ? WINDOW RECEPT? 210-62 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|