Plan Review Notes
Plan Review Notes For Permit 02090603
Permit Number 02090603
Review Stop P
Sequence Number 1
Notes
Date Text
2002-09-24 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT 1, EXECUTIVE TOILET ROOM SHALL BE
 ADAPTABLE. 11-4.1.3(11) PLEASE SHOW DE-
 TAILS FOR BACKING AT W/C & SHOWER FOR
 GRAB BARS, AND SEAT. 11-4.21.3/11-4.21.4
 SHOW DETAIL FOR SHR CONTROL 11-4.21.5
 AND CURB 11-4.21.7
 2) SHT 2, ELEVATION "C", LUNCH ROOM SINK
 SHALL COMPLY WITH 11-4.24 AND ALL SUB-
 SECTIONS. (HEIGHT, KNEE SPACE, CLEAR
 FLOOR SPACE ECT.)
 3) SHT 2 PLUMBING RISER TOILET ROOM,
 LUNCH ROOM SINK SHALL DRAIN DOWNSTREAM
 FROM THE W/C AND LAV IN THE WET VENTED
 SYSTEM. SEC. 909.1
 4) PLUMBING RISER EXEC.TOILET, SHOWER IS
 NOT VENTED. SHOWER SHALL BE TAKEN OFF
 BEFORE THE LAV. STACK.
 5) SHT 2 WATER ISOMETRICE, AIR CHAMBERS
 ARE NOT APPROVED. WATER HAMMER ARRESTORS
 ARE REQUIRED AT QUICK CLOSING VALVES,
 (ICE MAKERS, DISH WASHERS, WASH MACHINES
 ECT.) PER 604.9 AND IF USED SHALL BE
 LOCATED NEAR THE FIXTURE IN AN "EFFECT-
 IVE RANGE" NOT AT THE TOP OF DROP IN
 CEILING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377