| Plan Review Notes For Permit 02090590 |
| Permit Number |
02090590 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-13 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE A LOAD CALCULATION | | | SHOWING EXISTING LOADS AND ALL NEW | | | LOADS BEING ADDED.INCLUDE THE NAMEPLATE | | | RATINGS OF THE AHU & CONDENSING UNIT. | | | ALSO INDICATE THE SIZE OF THE EXISTING | | | SERVICE. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 | | | CALLED CONTRACTOR,GOT LOAD CALC,PANEL IS | | | 200 AMP,HEAT @10K,CALC@ 152 | | | AMPS,PASSED AND PRINTED. |
|