2002-09-13 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE A LOAD CALCULATION
 SHOWING EXISTING LOADS AND ALL NEW
 LOADS BEING ADDED.INCLUDE THE NAMEPLATE
 RATINGS OF THE AHU & CONDENSING UNIT.
 ALSO INDICATE THE SIZE OF THE EXISTING
 SERVICE.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392
 CALLED CONTRACTOR,GOT LOAD CALC,PANEL IS
 200 AMP,HEAT @10K,CALC@ 152
 AMPS,PASSED AND PRINTED.