Plan Review Notes
Plan Review Notes For Permit 02090563
Permit Number 02090563
Review Stop P
Sequence Number 1
Notes
Date Text
2002-09-27 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER. (DETAIL)
 2) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377