| Plan Review Notes For Permit 02090526 |
| Permit Number |
02090526 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-20 00:00:00 | FBC 412.6 REQUIRES A FIRE RATED ELEVATOR | | | LOBBY SEPARATION.SEE ALSO FBC | | | 412.6.2WITH REGARDS TO THE SECTION FOR | | | EXIT ACCESS WITHOUT TRAVEL THROUGH THE | | | LOBBY AS IT WOULD EFFECT THE SPACE | | | SHOWN AS "NIC"ON THE SOUTH SIDE OF THE | | | BUILDING. | | | | | | IF THE DEMISED SPACE SHOWN AS "NIC" IS | | | INTENDED FOR SEPARATE TENANTS, SHOW THE | | | FIRE RATED DOOR IN ACCORDANCE WITH FBC | | | 705.1.2. | | | | | | SECTIONS F/A2, 3/A3, AND 4/A3 DEPICT | | | VARIOUS FRAMING CONFIGURATIONS WITHOUT | | | SPECIFIC CONNECTION / FASTENER DETAILS | | | FOR ATTACHMENT TO THE STRUCTURE OR | | | OTHER FRAMING MEMBERS.SEE FBC 104.2.1. | | | | | | SEVERAL DETAILS SHOW THE USE OF WOOD | | | BLOCKING.SEE FBC 609.2.1 RE: FRT | | | LUMBER AND REVISE ACCORDINGLY. |
|