| 2004-06-23 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | NEC-99 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) SHTS P-2 & P-3 INSTA HOTS NOT APPROV- |
| | ED IN CLOSETS. NEC 99 SECTION 422-17. |
| | 2) SUBMIT MANUF. SPECIFICATION SHEETS |
| | FOR INSTA-HOTS. SECTION 303.4. |
| | 3) SHTS P-2, P-3, & P-4 FLOOR DRAINS IN |
| | THE LAUNDRY SHALL BE 3" MINIMUM. SECTION |
| | 412.4. CHANGE RISER DIAGRAM TO REFLECT |
| | THIS ALSO. |
| | 4) SHT P-4 DEEP-SEAL TRAP OR TRAP PRIMER |
| | REQUIRED PER SECTION 1002.4. INDICATE |
| | ONE OR THE OTHER ON NOTE #16 PLUMBING |
| | SPECIFICATIONS. |
| | 5) SHT P-4 SANT. RISER DIAGRAM, SHOW THE |
| | STANDPIPES AND CLEAROUTS REQUIRED BY |
| | SECTIONS 1002.1, 802.4 AND 708.10. THE |
| | CLEANOUTS SHALL BE 4' ABOVE THE FLOOR |
| | FOR ACCESS. |
| | 6) SHT P-5 INSTA-HOTS ARE NOT SHOWN AS |
| | LOCATED IN THE SAME LOCATION AS THE |
| | WATER HEATERS WERE LOCATED. REVISE THE |
| | WATER RISER DIAGRAM TO REFLECT THE FLOOR |
| | PLAN FOR THE NEW LOCATION OF THE INSTA- |
| | HOTS. SHOW THE LOCATION OF THE REQUIRED |
| | WATER HAMMER ARRESTORS ON THE NEW RISER |
| | DIAGRAM. SECTION 104.2.1 |
| | 7) THE SIGNATURE OF THE ARCHITECT IS RE- |
| | QUIRED PER FAC 61G1-16.003 & FS 481.2055 |
| | INITIALS ARE NOT ACCEPTABLE. - PROVIDE |
| | A SIGNED, SEALED, DATED, AND NOTORIZED |
| | LETTER INDICATING THAT THIS IS YOUR LEG- |
| | AL SIGNATURE FOR OUR ARCHITECT/ENGINEER |
| | SIGNATURE FILE. - THIS HAS BEEN REQUEST- |
| | ED PREVIOUSLY PER DEWEY PALMER, ELECTRI- |
| | CAL PLAN REVIEWER. |
| | |
| | REVIEW BY KEN STEVENS |