| 2005-06-01 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)IT IS NOT CLEAR WHAT DESIGN |
| | PROFESSIONAL IS CERTIFYING THE STRENGTH |
| | OF THE DESIGN.NO TITLE BLOCK, |
| | ENGINEERED CALCULATIONS, DESIGN CRITERIA |
| | PER FBC (FBC1608.2.1(1-3), |
| | FBC1608.2.2(1-4))OR SEAL WAS PROVIDED. |
| | |
| | 2.) THE RAILING SHOPS DO NOT HAVE THE |
| | JOB NAME ON THEM.WHERE WILL THIS BE |
| | INSTALLED? |
| | |
| | 3.) PAGE 1, PROVIDE HANDRAIL HEIGHT |
| | FBC1007.5.HANDRAILS REQUIRED BOTH |
| | SIDES. |
| | |
| | 4.)FBC1007.5.5, HANDRAIL SHALL |
| | CONTINUE TO SLOPE FOR A DISTANCE OF |
| | DEPTH OF ONE RISER AT THE BOTTOM. |
| | |
| | 5.)PAGE 2, DIMENSIONS REQUIRED BY |
| | FBC1015 ARE NOT ON THE PLAN.WHAT IS |
| | THE LOCATION FOR THE HANDRAIL SHOWN AT |
| | THE BOTTOM OF PAGE 2? |
| | |
| | 6.)PAGE 3 GUARDRAIL APPEARS TO BE |
| | DESIGNED WITHOUT THE REQUIREMENT (REJECT |
| | A 4" OBJECT BETWEEN PICKETS) FBC1015.3. |
| | PLEASE GIVE LOCATIONS FOR THE |
| | RAILINGS/GUARDRAILS SUBMITTED. |
| | |
| | 7.)DESIGN CRITERIA ON COVER SHEET IS |
| | NOT COMPLIANT FOR EITHER HANDRAILS OR |
| | GUARDRAILS. |
| | |
| | 8.)HANDRAILS REQUIRED BOTH SIDES, |
| | FBC1007.5.2. |
| | |
| | 9.)ON THE MULLION NOA, PLEASE INDICATE |
| | WHICH PRODUCT(S) YOU ARE USING.NOT ALL |
| | ARE COMPLIANT FOR THE SIZES TO BE |
| | INSTALLED. |
| | |
| | 10.) A REVISION FEE WAS CHARGED FOR THE |
| | PRODUCT APPROVALS (CHANGE FROM APPROVED |
| | PLAN/SPEC). |
| | |
| | |