| 2003-01-29 00:00:00 | *************** UNSAT **************** |
| | |
| | PLEASE SEE THE FOLLOWING NOTES, THERE |
| | ARE NOTES FROM FIRST TWO REVIEWS THAT |
| | WERE NOT ADDRESSED. PLEASE SEE THE |
| | ATTACHED LETTER WITH RESPECT TO DESIGN |
| | PROFESSIONALS UNDER FS.553-80(2)(B). |
| | THIS IS THE 3RD TIME THESE PLANS HAVE |
| | BEEN IN FOR REVIEW. |
| | |
| | 1)NOTE: PLEASE SEE PANEL "E", SHOWN AS |
| | 30 CIRCUIT AND 24 CIRCUIT. PLEASE REVISE |
| | |
| | 2)NOTE: IT IS NOTED THAT THERE IS A NOTE |
| | MENTIONING ALL EM/EX LTS TO BE WIRED ON |
| | SAME BRANCH CIRCUIT AHEAD OF SWITCHING. |
| | HOWEVER PLAN CIRCUITING DOES NOT |
| | CORRELATE WITH THIS NOTE?? |
| | |
| | 3)NOTE: PLEASE SUBMIT AND SHOW ALL AIC |
| | RATINGS FOR ALL NEW EQUIPMENT BEING |
| | INSTALLED. MAINS, BRKRS, PANELS ARE |
| | ALL TO BE RATED FOR THE AVAIABLE FAULT |
| | CURRENT. 110-9 |
| | |
| | 4)NOTE; PLEASE SEE SD IN UNIT "B", |
| | SHOWN IN KITCHEN AND W/IN 3'OF BATHROOM |
| | DOOR. PLEASE RELOCATE TO A MIN OF 3' |
| | FROM BATH DOOR AND OUT OF KITCHEN. |
| | SD MAY BE MOVED JUST INTO LIVING ROOM |
| | AREA. NFPA-72 8-1.4.1.6 |
| | |
| | 5)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | PROTECTED CIRCUITS ON PANEL SCHEDULE |
| | PER 210-12. IT WAS NOTED ON PLAN BUT |
| | NEEDS TO BE ON PANEL SCHEDULES. |
| | |
| | 6)NOTE: PLEASE ADDRESS COMMENT FOR FHAR |
| | 24 CFR 100.205. REQ`MENTS ARE TO BE |
| | NOTED ON PLANS. RECEPT AND SWITCH HEIGHT |
| | (S) ARE 18 AND 48" WHICH CONFORM, BUT |
| | THERE ARE OTHER REQ`MENTS. PLEASE NOTE |
| | ON PLANS FHAR. |
| | |
| | 7)NOTE: PLEASE CLARIFY WHERE LOAD |
| | CALCULATIONS ARE FOR HOUSE PANELS.?? |
| | 215-5 |
| | |
| | 8)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR BETWEEN MAIN DISC |
| | AND HOUSE PANEL. SIZE PER 250-122 |
| | |
| | 9)NOTE: PLEASE SEE PLANS, PANEL SCHEDULE |
| | -S AND RISER DIAGRMA DO NOT INDICATE |
| | HOW PANEL "E" IS FED?? PLEASE REVISE. |
| | NOT SHOWN COMING FROM PANEL HS? |
| | PLEASE CLARIFY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. ONCE AGAIN, IF THERE ARE ANY |
| | QUESTIONS, OR IF A MEETING IS DESIRED |
| | TO GO OVER COMMENTS, PLEASE CALL. |
| | |
| | DEWEY PLAMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |