| Date |
Text |
| 2002-10-05 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | |
| | 1) SHT A-1 A DRINKING FOUNTAIN IS REQUI- |
| | RED PER TABLE 403.1 |
| | 2) SHTS A-2, A-3, & A-4, SHOW COMPLIANCE |
| | 0F FAIR HOUSING GUIDELINE REQUIREMENTS |
| | 1 THRU 7. INDICATE SPECIFICATION "A" OR |
| | "B" BATHROOMS FOR ALL UNITS. SHOW BACK- |
| | ING PER REQUIREMENT 6. SHOW CLEAR FLOOR |
| | SPACE FOR ALL KITCHEN AND BATHROOM FIX- |
| | TURES. INDICATE IF THERE WILL BE KNEE |
| | SPACE AT LAV'S OR NOT. IF NOT, (PARALLEL |
| | APPROACH), THE LAV WILL BE CENTERED IN |
| | THE 48" CLEAR FLOOR SPACE. |
| | 3) SHT A-5 A DRINKING FOUNTAIN SHALL BE |
| | REQUIRED IN OFFICE. TABLE 403.1 |
| | 4) SHT A-8 PLEASE PROVIDE CALCULATIONS |
| | FOR PRIMARY AND SECONDARY ROOF DRAINS |
| | PER SEC'S 1106 AND 1107. SHOW AREA FOR |
| | ALL VERTICAL WALLS ADDED TO CALCULATIONS |
| | 5) SHT P-1 PLUMBING NOTES #7, AIR CHAM- |
| | BERS ARE NOT APPROVED. PLEASE DELETE RE- |
| | FERENCE. |
| | 6) SHT P-4 PLUMBING SPECIFICATIONS #15 |
| | AIR CHAMBERS ARE NOT APPROVED, PLEASE |
| | DELETE REFERENCE. |
| | 7) PLEASE PROVIDE A WATER RISER DIAGRAM. |
| | SHOW ALL FIXTURES, AND PIPE SIZES. SHOW |
| | REQUIRED WATER HAMMER ARRESTORS PER SEC. |
| | 604.9. LOCATION TO BE NEAR THE FIXTURE |
| | IN AN "EFFECTIVE RANGE" NOT AT TOP OF |
| | RISER OR ON MAIN LINES ABOVE CEILING PER |
| | PDI-WH 201 AND MANUFACTURE INSTALLATION |
| | INSTRUCTIONS. |
| | 8) PLEASE SUBMIT A STORM RISER DIAGRAM. |
| | SHOW ALL PIPE SIZES AND SHOW SQUARE FEET |
| | AS IT ACCUMULATES IN SYSTEM. INDICATE |
| | WHERE STORM LINES WILL BE TIED IN OUT- |
| | SIDE OF BLDG. |
| | 9) PLEASE SUBMIT A CONDENSATE RISER DIA- |
| | GRAM. CONDENSATE SHALL BE PIPED SEPARAT- |
| | ELY OUT OF BLDG. AND TIE INTO STORM, |
| | CATCH BASIN, OR DRYWELL. A RELIEF VENT |
| | IS REQUIRED AS CONDENSATE EXITS BLDG. |
| | 10) PLEASE SUBMIT RISERS FOR RELIEF |
| | VALVE DISCHARGE, AND EMERGENCY PAN DRAIN |
| | LINES. SECS. 504.7.1 & 504.8.1 - T/P |
| | LINE SHALL NOT BE TRAPPED. INDICATE MAT- |
| | ERIAL USED FOR RISERS. |
| | 11) PROVIDE A WATER HEATER DETAIL SHOW- |
| | ING COMPLIANCE WITH 607.3 THERMAL EXPAN- |
| | SION CONTROL. ALSO SEE 607.3.2 |
| | 12) SHT PLEASE SHOW DRAINAGE FIXTURE |
| | UNITS AS THEY ACCUMULATE IN SYSTEM. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |